6.8
Entering the tank data at the remote indicator
Unimes E
Zero calibration has been performed.
The pointer of the direct indication gauge points to 100 %.
Tank shape
The arrow at the bottom of the display points to the unit "Litres".
The display shows the code of the selected tank shape. When
the unit is commissioned for the first time, the displayed code is
0. Code 0 means that no tank shape has yet been selected.
1.
Use the keys
mined. Refer to chapter 6.1, page 11.
2.
Press the F key to accept the setting and continue with the tank
volume.
Tank volume
The arrow at the bottom of the display points to the unit m³.
The display shows the currently selected tank volume. 0000
means that no tank volume has yet been entered.
1.
Use the
and
cility. By pressing the
changed. The
within a range from 0 to 9.
2.
Up to a volume of 9999 litres, the volume is entered in litres
without decimal places. In the case of volumes of > 9999 litres,
the value is entered in cubic metres with a decimal place (1000
litres = 1 cubic metre). The decimal place is moved with the
key.
3.
Press the F key to accept the setting and continue with the tank
height.
Tank height
The arrow at the bottom of the display points to the unit "Per-
cent". The display shows the currently selected tank height.
0000 means that no tank height has yet been entered.
1.
Set the tank height in mm with the
key, you can select the digit to be changed. The
you to change the selected digit within a range from 0 to 9.
2.
Press the F key to accept the setting and continue with the cur-
rent level.
and
to set the code of the tank shape deter-
keys to enter the total volume of the tank fa-
key, you can select the digit to be
key allows you to change the selected digit
Mounting and commissioning
keys: By pressing the
key allows
15