SKYCHARGE Mobile – TECHNICAL DOCUMENTATION

2 CONNECTION TO THE GRID

The SKYCHARGE Mobile is equipped with a 10m supply cable. The connection to the grid is done through a 32 A, 5
poles, 400 V, 6h CEE plug.
Connect the station to the grid with the following protections:
Model
Input voltage
Input current
Circuit breaker at panel (1)
Residual Current Mandatory Device
(1) The Installer must define the types of Circuit breaker.
The circuit breakers at panel of 40 A overvalued in order to ensure the functioning of the charging station
with a temperature increase.
Please be sure to install a mandatory RCD device after the C40 breaker.
Green Motion strongly recommends using a Doepke RCCB DFS 4 040-4/0.03-A EV R as an RCD device or Eaton
167897 FRCDM-40/4/03-G/B.
NOTE FOR SWITZERLAND
● The NIBT standard does not requires DC terminals to be protected against direct fault currents.
22 kW
400 V
AC
32 A
rms
C40
Doepke RCCB DFS 4 040-4/0.03-A EV R
Or
Eaton 167897 FRCDM-40/4/03-G/B