EWS-102 CONTROL UNIT
To begin the system setup,
press the
and
buttons together
Press the
Load Calibra�on
A�er placing the known load within the elevator cabin, press the
When the dashes are displayed, set the value of the required load in kilograms. Use the
select the required digit (selected digit flashes) and use the
For example: Using a known load of 75Kg
To complete the ac�on, press the
Countdown
The instruments then counts down from 10 to 1
Upon comple�on, the screen will display
return to Opera�on Mode. The load has now been calibrated.
Firmware 5.5 Rev 2 Booklet subject to alteration
bu�on to enter load calibra�on menu
x 7
x 5
bu�on
Mul� Analog version only: See note 3 page 1. A�er the EWS 102 calibra�on
and setup has been completed, place the the li� at the lowest floor level and
rezero following the process on page 2, this will finalise the Analog output
calibra�on.
CALIBRATION LOAD
Bu�on to proceed.
bu�on to set the required digit value.
CAL
for approximately 10 seconds and then the system will