8.2
To reference the source and two meters:
Step 1:
Clean and insert the SC-end of
the SC to LC jumper (Reference
Jumper no. 1, or RJ1) into the
output of the light source.
Step 2:
Clean and insert the LC end
of RJ1 jumper into the LC port
adapter of Meter no. 1 (M1)
(Figure 8).
For multimode only: Wrap the jumper 5
times and secure it in a 25 mm mandrel
with tape (standard 50 µm multimode
procedure).
Step 3:
Verify that RJ1 is acceptable at your system's wavelength(s) and reference this
power to 0.00 dB.
Step 4:
Disconnect and move the meter-end LC of RJ1 to Meter no. 2 (M2) and repeat
Step 3. Disconnect M2 after this step.
Step 5:
Clean and insert the LC end of RJ1 into an LC adapter.
Step 6:
Clean and install an LC to LC
jumper-Reference Jumper no.
2 (RJ2) into M1 and the LC
adapter (Figure 9).
Step 7:
Verify that the RJ1/ RJ2 mated
pair are acceptable with a loss
≤0.15 dB.
Step 8:
Disconnect RJ2's LC
connector from the LC adapter
and protect it with a clean dust
cap until you are ready to start
the system testing.
Step 9:
Clean and install an LC to LC
jumper-Reference Jumper
no.3 (RJ3) into M2 and the LC
adapter (Figure 10).
Step 10: Verify that the RJ1/RJ3 mated
pair are acceptable with a loss
≤0.15 dB.
Step 11:
Disconnect RJ1's LC connector
from the LC adapter and protect
it with a clean dust cap.
Step 12: Leave the LC adapter on the
end of RJ3 for the remainder
of this procedure since it will be
required for mating to the TAP
port test harness.
STANDARD RECOMMENDED PROCEDURE 003-137-AEN | ISSUE 1 | JANUARy 2017 | PAGE 6 OF 8
22 mm mandrel wrap for multimode only
Do NOT
disconnect
Light Source
(Tx)
HPA-0758
multimode only
RJ1
Do NOT
disconnect
Light
Source
HPA-0759
Dust cap
multimode only
RJ 1
Do NOT
disconnect
Light Source
HPA-0760
Reference
Jumper no.1
RJ1
0.00
Meter no. 2
Meter no. 1
(RX)
(RX)
M1
LC
adapter
Reference
Jumper no. 2
RJ2
Do NOT
disconnect
Figure 9
Do NOT
disconnect
LC
adapter
RJ3
0.3 dB
0.15 dB
M2
Figure 10
M2
Figure 8
0.15 dB
M1
RJ2
M1