NOTE: Calculate the Z dimension carefully. Once the kit is installed, any adjustment needed along the Z axis will
require that the housing be removed.
TPA-5834
Step 6: Once the kit is secured in position, install the EDGE™ housing, as applicable, or any other device that
has the ability to be installed into a 19-in rack space. Slide the housing over the support bars into the
mounting kit. The bars will hold the housing while securing the mounting brackets on each side into
the mounting holes on front of the kit. If installing only one housing, place it in the top position.
NOTE: If the lowest housing is not supported by the support bars, remove and reinstall the support bars directly
below the housing as described in Section 4.
6.
Rackless Ladder Rack Mounting Kit 2U or 4U
1
2U
Z Axis
X Axis
Step 1:
Loosen the screws as shown in Figure 4 to allow the rails to slide.
TPA-5835
Step 2:
Place the mini-frame in the middle of the cross members. Slide the omega brackets to the left and
right to lock the system in the horizontal (X) axis.
NOTE: The kit is able to move in X and Z directions.
Screwdriver
2
1
4U
Z Axis
X Axis
Standard Recommended Procedure 003-809 | Issue 7 | May 2017 | Page 4 of 6
Figure 3
Screwdriver
2
Figure 4