WARNING: DO NOT over tighten water fittings.
Mount chiller on a flat pad and away for water spray.
Give at least 1 ft all the way around unit for servicing.
Install evaporator water inlet and outlet.
Install condenser water inlet and outlet.
Test water fittings for leaks.
Apply electrical power to the chiller.
Adjust the controller to the desired water temperature. (See "Operation and Programming")
Important:
Regulate condenser water until pressure on the pressure gauge reads between 115 to 125 PSIG for models
DS-4-WCMD thru DS-9-WCMD and 195 to 220 PSIG for model DS-10-WCMD. Check after 15 minutes of run time,
adjust the water flow (if needed) to the correct pressure.
Warning: This unit must have proper water flow rate both on the evaporator and
the condenser to operate correctly.
CHILLER SET-UP AJUSTMENTS