Installation
Choosing a Suitable Location
The MWS3A-AT-PRM is designed to be ceiling mounted
and must satisfy the following criteria:
Avoid positioning the unit where direct sunlight may
enter the sensor element.
Do not site the sensor within 1m of any lighting, forced
air heating or ventilation.
Do not fix the sensor to an unstable or vibrating
surface.
Position the sensor so that the occupants of the room
fall inside the detection zone shown in below.
Note that the detection zone illustrated is based on a
recommended mounting height of 2.8m. A lower height
will decrease the overall size of the detection zone.
Detection diagrams
30m
6m
30m
6m
Sensitivity set to 80%
Detector head position set to 40°
Sensitivity set to 80%
Detector head position set to 40°
Ideal for large office or classroom
Sensitivity set to maximum
Detector head position set to 0°
Sensitivity set to maximum
Detector head position set to 0°
Ideal for open plan areas and offices
2
19m
6m
19m
6m
6m
17m
6m
17m
Sensitivity set to maximum
Detector head position set to 80°
Sensitivity set to maximum
Detector head position set to 80°
Ideal for corridor or aisle applications
Note. If the range is compromised by the ceiling construction /
material. Add the supplied 20mm spacer ring. See page 3 for
fitting details.
6m
23m
6m
23m