EarthLinked HCM-1860C 설치 및 유지 관리 매뉴얼 - 페이지 6

{카테고리_이름} EarthLinked HCM-1860C에 대한 설치 및 유지 관리 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. EarthLinked HCM-1860C 13 페이지. Hybrid cooling module

Installation - Placement

The Hybrid Cooling Module unit is placed as shown in Figure 2 relative to other components in
®
the EarthLinked
system. The Hybrid Cooling Module is located outdoors and will be
connected to the refrigerant line set (vapor tube) outside the building.
Figure 2. Hybrid Cooling Module Placement in EarthLinked
NOTES:
All refrigerant and water lines between these above ground components must be
insulated with at least 1/2" wall thickness Armaflex, Insul-Tube or equivalent
insulation. Thicker insulation is recommended for the Compressor Unit-to-Air Handler
refrigeration lines for sound isolation
If you plan to exceed the 40 ft. max elevation of the Air Handler, please contact our
Tech Support Department. Increased height will reduce performance and shall be
factored into system sizing
The Hydronic Water Module (HWM) shall always be mounted above the Compressor
Unit, never below.
HCM-IMM (10/16)
®
System
6