Dell PowerVault 2xxS Storage Systems SCSI Backplane Board Replacement Instructions
1. Carefully insert the replacement enclosure services module into the mod-
ule bay. Push the module all the way to the back of the bay until it is seated
in the connector.
2. Using a Phillips-head screwdriver, tighten the captive screw at the top of
the enclosure services module to secure the module to the chassis.
3. Repeat steps 1 and 2 to install the remaining enclosure services module.

Install the Cooling Fans

NOTICE: In a nonredundant system, install the cooling-fan blank in
the same cooling-fan bay from which it was removed.
NOTE: In a redundant storage system, there are three cooling fans. In a nonre-
dundant storage system there are two cooling fans and one cooling-fan blank.
Because a cooling fan and a cooling-fan blank are installed in the same manner,
both components are referred to as a cooling fan in this procedure.
To install the cooling fans, perform the following steps:
1. Carefully slide the cooling fan into the empty cooling-fan bay. Push the
cooling fan all the way to the back of the bay until it is seated in the
connector.
2. Using a Phillips-head screwdriver, turn the two captive screws clockwise
until the cooling fan is secured to the cooling-fan bay.
3. Repeat steps 1 and 2 to install the remaining cooling fans.

Install the Power Supplies

NOTICE: In a nonredundant system, install the power supply and the
power-supply blank in the same power-supply bays from which they
were removed.
NOTE: In a redundant storage system, there are two power supplies. In a non-
redundant storage system there is one power supply and one power-supply
blank. Because a power supply and a power-supply blank are installed in the
same manner, both components are referred to as a power supply in this
procedure.
To install the power supplies, perform the following steps:
1. Carefully slide the power supply into the empty power-supply bay. Push the
power supply all the way to the back of the bay until it is seated in the
connector.
2. Using a Phillips-head screwdriver, turn the two captive screws clockwise
until the new power supply is secured to the power-supply bay.
3. Repeat steps 1 and 2 to install the remaining power supply.