ABB FIO-01 빠른 시작 매뉴얼 - 페이지 3

{카테고리_이름} ABB FIO-01에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB FIO-01 12 페이지. Digital i/o extension
ABB FIO-01에 대해서도 마찬가지입니다: 빠른 매뉴얼 (14 페이지)

ABB FIO-01 빠른 시작 매뉴얼
• Insert the module carefully into the option slot on the control
board until the retaining clips lock the module into position.
• Fasten the screw (included) to the stand-off.
Note: Correct installation of the screw is essential for fulfilling the
EMC requirements and for proper operation of the module.

Terminal designations

Marking
X61, X62, X63,
X64
1
2
X65, X66
1
2
3
Wiring
Maximum cable size is 1.5 mm
2.5 mm
connected to the JCU-01 Control Unit. See the drive Hardware
Manual for more information.
Tightening torque is 0.3 N·m (2.7 lbf·in) for the digital I/O plugs
and 0.5 N·m (4.4 lbf·in) for the relay plugs.
Programming
The communication between the module and the drive is activated
by a drive parameter. See the drive Firmware Manual.
Description
• DIOx = Digital I/O. Input (default), push-pull or
open collector. Selection is made by parameter.
See the drive firmware manual for more
DIOx
information.
COM
• COM = Ground reference on option board
ROxNO
ROxCOM
ROxNC
2
(AWG 14) for relays. The cable shields should be
• ROxNO = Relay normally open
• COM = Common
• ROxNC = Relay normally
connected
2
(AWG 16) for digital signals and
Quick guide - FIO-01
3