HP 1405-5 설치 및 시작하기 매뉴얼 - 페이지 33

{카테고리_이름} HP 1405-5에 대한 설치 및 시작하기 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. HP 1405-5 44 페이지. 1405 switch series
HP 1405-5에 대해서도 마찬가지입니다: 빠른 시작 매뉴얼 (16 페이지), 설치 및 시작하기 매뉴얼 (45 페이지)

HP 1405-5 설치 및 시작하기 매뉴얼
Table A-1. Cabling Specifications
Twisted-pair copper
Cabling and Technology Information
Specifications
10 Mbps Operation
100 Mbps Operation
1000 Mbps Operation
Note on 1000BASE-T Cable Requirements. The Category 5 networking
cables that work for 100BASE-TX connections should also work for
1000BASE-T, as long as all four-pairs are connected. But, for the most robust
connections, you should use cabling that complies with the Category 5e
specifications, as described in Addendum 5 to the TIA-568-A standard (ANSI/
TIA/EIA-568-A-5).
Because of the increased speed provided by 1000BASE-T (Gigabit-T), network
cable quality is more important than for either 10BASE-T or 100BASE-TX.
Cabling plants being used to carry 1000BASE-T networking must comply with
the IEEE 802.3ab standards. In particular, the cabling must pass tests for
Attenuation, Near-End Crosstalk (NEXT), and Far-End Crosstalk (FEXT).
Additionally, unlike the cables for 100BASE-TX, the 1000BASE-T cables must
pass tests for Equal-Level Far-End Crosstalk (ELFEXT) and Return Loss.
When testing your cabling, be sure to include the patch cables that connect
the switch and other end devices to the patch panels on your site. The patch
cables are frequently overlooked when testing cable and they must also
comply with the cabling standards.

Cabling and Technology Information Specifications

Category 3, 4 or 5, 100-ohm unshielded twisted-pair (UTP) or
shielded twisted-pair (STP) cable, complying with IEEE 802.3
10BASE-T specifications.
Category 5, 100-ohm UTP or STP cable, complying with IEEE 802.3u
100BASE-TX specifications.
Category 5, 100-ohm 4-pair UTP or STP cable, complying with IEEE
802.3ab 1000BASE-T specifications—Category 5e or better is
recommended. See note on 1000BASE-T Cable Requirements
below.
Specifications
A-3