Figure 22 Connect the grounding cable to the grounding strip
(1) Grounding post
(3) Grounding cable
CAUTION:
Only the grounding cables supplied with the HP V1910-24G-PoE (365W) Switch JE007A and HP
V1910-24G-PoE (170W) Switch JE008A provide OT terminals at the ends connecting the grounding
strip. For other switch models, prepare proper OT terminals by yourself.
Connect the grounding cable to the grounding system in the equipment room. Do not connect it to a fire
main or lightning rod.
Grounding the switch with a grounding conductor buried in the
earth ground
If the installation site has no grounding strips, but earth ground is available, hammer a 0.5 m (1.64 ft) or
longer angle iron or steel tube into the earth ground to serve as a grounding conductor.
The angle iron must have a dimension no less than 50 × 50 × 5 mm (1.97 × 1.97 × 0.20 in) and the steel
tube must have a wall thickness no less than 3.5 mm (0.14 in) and be zinc-coated.
Weld the yellow-green grounding cable to the angel iron or steel tube and treat the joint for corrosion
protection.
Figure 23 Ground the switch by burying the grounding conductor into the earth ground
(1) Grounding screw
(4) Joint
(2) Grounding strip
(4) Hex nut
(2) Grounding cable
(5) Grounding conductor
22
(3) Earth
(6) Switch rear panel