Epever SHI3000 사용자 설명서 - 페이지 10

{카테고리_이름} Epever SHI3000에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Epever SHI3000 20 페이지. Shi series pure sine wave inverter

Epever SHI3000 사용자 설명서
Alarms
Alarms
Buzzer
Sounds
The buzzer stops after 20S.
Protections
Overload or Output Short Circuit Protection
Overload
Character
Continuance
Recover 3
times
If the overload or short circuit status still remains when the inverter
tries to recover for 3 times, you should reduce or clear the loads
and then restart the inverter manually. Load over than 250% will be
treated as output short circuit.
Overload or Short circuit, No Output
Over or Low input voltage, No Output
Over temperature, No Output
Inverter Fault, No Output
125%
150%
60S
10S
Space 5 seconds for the first time, 10 seconds
for the second time, and 15 seconds for the
Status
200%
3S
third time
8
>250%
230%
<0.2S
0.01S