EPHESUS Arena 650 설치 지침 매뉴얼 - 페이지 8

{카테고리_이름} EPHESUS Arena 650에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. EPHESUS Arena 650 16 페이지. All field led luminaire

Installation Instructions - All Field LED Luminaire
Equipment Required:
3/16" Allen driver (or metric equivalent)
Power cable
Electrical splicing connectors. For all outdoor installations, silicone filled water resistant connectors are highly
recommended.
Figure 6. Electrical Connections
Power wiring
Incoming power cable shall be SOOW style 3C cable with a minimum of 14AWG annealed stranded bare copper per ASTM
B-174 with a minimum temperature range of -40°C to +90°C. Cable must be water resistant, UV rated/sunlight resistant, UL
listed and CSA certified for indoor and outdoor use. International applications shall be harmonized (HAR) or IEC equivalent.
1.
Remove cover from junction box at the base of the luminaire.
2.
Route incoming power cable through the cord grip in the junction box cover.
3.
Strip outer jacket of incoming power cable back 3" (7cm). Connect the incoming power wires to the fixture power wires
on right side of junction box.
NEVER connect the fixture's green insulation (GROUND) wire to the black (LINE) current-carrying or white
(NEUTRAL) supply wire, as this could energize the metal housing and create the risk of electrical shock. FAILURE TO
FOLLOW THIS WARNING MAY LEAD TO DEATH, SEVERE INJURY, OR PROPERTY DAMAGE.
8
EATON
MN507001EN
Fixture Junction Box
Fixture power wire color
Black
White
Green
Power wiring connections
Installation instructions rev 170117
Power Cord Grip
Designation
Line
Line or Neutral
Ground
WARNING