ABB ATS Annunciator 빠른 시작 매뉴얼 - 페이지 7

{카테고리_이름} ABB ATS Annunciator에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB ATS Annunciator 12 페이지. Modbus; ats annunciator monitors and controls up to 8 automatic transfer switches equipped with the mx150/250 controller.

ABB ATS Annunciator 빠른 시작 매뉴얼
Information
MODBUS Networks
Networks may be either Singly Terminated or Doubly Terminated.
The Annunciator has two separate MODBUSs.
• ATS MODBUS connects to ATSs. - 8 max.
• PC MODBUS connects a PC to Annunciators - max 32.
PC
AA
AA
ATS
ATS
ATS
Network Termination
Cables:
• 300V rated insulation - Belden 9463
• 600V rated insulation - Belden 3072F
Resistors: 105Ω
Singly Terminated Network (Daisy Chain)
Maximum Total Network Cable Length: 500 M (1,640 ft)
AA
ATS
ATS
ATS
ATS
ATS
PC MODBUS Network - 1 per network
Annunciators - max 32 per network
ATS MODBUS Network - 1 per Annunciator
ATS MODBUS Network - 1 per Annunciator
ATSs - max 8 per Annunciator
ATS MODBUS Network - 1 per Annunciator
ATSs - max 8 per Annunciator
Doubly Terminated Network (Daisy Chain)
Maximum Total Network Cable Length: 2,700 M (8,850 ft)
7