ABB Jocab Safety Vital 3 매뉴얼 - 페이지 3
{카테고리_이름} ABB Jocab Safety Vital 3에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB Jocab Safety Vital 3 14 페이지. Safety controller
ABB Jocab Safety Vital 3에 대해서도 마찬가지입니다: 작동 지침 (11 페이지)
Reset connections – Vital 1
Manually supervised reset
The manually supervised reset contact
connected to input X1 must be closed
and opened in order to activate the relay
outputs.
Output connection – Vital 1
Relay outputs
The Vital 1 has two (2 NO) safety outputs.
In order to protect the output contacts
it is recommended that loads (inductive)
are suppressed by fitting correctly chosen
VDR's, diodes etc. Diodes are the best arc
suppressors, but will increase the switch-off
time of the load.
Connection of S1
Even
number
of
units
(Eden+Spot+Tina) requires a connection
between B1 and S1. S1 is not connected
at odd number of units.
See drawing below figure A and other
examples in the book
Connection examples of safety devices to Vital 1
5:8
Automatic reset
Automatic reset is selected when B1, X1
and X4 are connected. The relay outputs
are then activated at the same time as the
inputs.
Information outputs
+24V
B1
0V
B2
Vital 1 has a switching relay output for
information. The function is determined by
a DIP switch.
The DIP switch position 1 (original position)
is the information output Y14 internally con-
nected to 0V and +24 V as per:
• Y14 is closed to 0V (B2) internally when
in
series
Vital 1 has not been reset.
• Y14 is closed to +24 V (B1) when Vital
1 has been reset.
Y14
Vital 1
0V
Testing external contactor status
B1
Contactors, relays and valves can be
supervised by connecting 'test' contacts
between B1 and X1. Both manually
supervised and automatic reset can be
used.
Y14
+24V
B1
Vital 1
0V
B2
0V
In DIP switch position 2 (the purpose of
the function is to start/restart block, RES)
the information output Y14 is internally con-
nected to 0V and +24 V as per:
• Y14 is internally closed to 0V (B2) when
the dynamic safety loop is open or when
the dynamic safety loop is closed and Vital
1 has been reset.
• Y14 is internally closed to +24 V (B1) when
the dynamic safety loop is closed but Vital
1 has not been reset (RES).
0V
ABB