CREE LIGHTING C-LITE C-WR-B-WLIN4-SCCT Series 설치 지침 매뉴얼 - 페이지 5
{카테고리_이름} CREE LIGHTING C-LITE C-WR-B-WLIN4-SCCT Series에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. CREE LIGHTING C-LITE C-WR-B-WLIN4-SCCT Series 19 페이지.
INSTALLATION INSTRUCTIONS
C-WR-B-WLIN4-SCCT LED Series
NOTE: The emergency driver and AC driver
must be fed from the same branch circuit.
Make the following Electrical Connections:
STEP 1:
a. Connect the black fixture lead labeled
unswitched hot to the unswitched
voltage supply lead.
b. Connect the black fixture lead labeled
switched hot to the switched voltage
supply lead.
c. Connect the white fixture lead to the
neutral supply lead (Hot 2 for 208/240V
wiring).
d. Connect the bare or green ground fixture
lead to the supply ground lead.
e. If 0/1-10V Dimming is used, connect the
violet fixture lead to the supply positive
dimming lead. If dimming is not being
used ensure to cap off the violet
fixture lead. Class 1 wiring must be used
for dimming connections.
f.
If 0/1-10V Dimming is used, connect the
grey or pink fixture lead to the supply
negative dimming lead. If dimming is not
being used ensure to cap off the grey or
pink fixture lead. Class 1 wiring must be
used for dimming connections
Tuck all wires carefully into wiring chamber
ensuring that no wires are pinched..
ELECTRICAL CONNECTIONS-
Emergency Driver, No Occupancy Sensor
http://lighting.cree.com/warranty
Document:
LPN00601X0001A2_A
Created By:
TMT
LUMINAIRE
LINE- UNSWITCHED
LINE-BLACK
UNSWITCHED
LINE SWITCHED
LINE-BLACK
NEUTRAL OR
HOT 2
GREEN/YELLOW
GROUND
DIM (+)
DIM (-)
|
866.924.3645
Date:
7-26-2021
SWITCHED
WHITE
BARE OR
VIOLET
GREY OR
PINK