Calibration
Calibration is a process during which a device learns the position of the limit switches and a
motor characteristic.
Calibration is mandatory in order for the device to correctly recognize a roller blind position.
The procedure consists of an automatic, full movement between the limit switches (up, down,
and up again).
Note: If you notice the calibration process fail (e.g. it does not start, movement times are really
short or highly inaccurate), adjust parameter 155 value (e.g. reduce it by half).
Standard roller blind positioning
Calibration using a connected momentary switch
1. Make sure:
o
the device is supplied,
o
the momentary switch is connected to S1 and S2 terminals,