Installing the Device

This chapter describes how to install the device, including mounting the device,
connecting power, and connecting the device to the network.
Electrocution hazard – risk of serious personal injury and/or damage to
equipment
Before performing any maintenance tasks, make sure all power to the device has
been disconnected and wait approximately two minutes for any remaining energy
to dissipate.
IMPORTANT
This product contains no user-serviceable parts. Attempted service by unauthorized
personnel shall render all warranties null and void.
Changes or modifications not expressly approved by Siemens AG could invalidate
specifications, test results, and agency approvals, and void the user's authority to
operate the equipment.
IMPORTANT
This product should be installed in a restricted access location where access can only
be gained by authorized personnel who have been informed of the restrictions and
any precautions that must be taken. Access must only be possible through the use
of a tool, lock and key, or other means of security, and controlled by the authority
responsible for the location.
2.1

Mounting the Device

The RUGGEDCOM RS8000T is designed for maximum mounting and display
flexibility. It can be equipped with connectors that allow it to be installed in a 48 cm
(19 in) rack, 35 mm (1.4 in) DIN rail, or directly on a panel.
IMPORTANT
Heat generated by the device is channeled outwards from the enclosure. As such, it
is recommended that 2.5 cm (1 in) of space be maintained on all open sides of the
device to allow for some convectional airflow.
Forced airflow is not required. However, any increase in airflow will result in a
reduction of ambient temperature and improve the long-term reliability of all
equipment mounted in the rack space.
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
DANGER
2
7