Siemens SITRANS L 사용 설명서 - 페이지 25
{카테고리_이름} Siemens SITRANS L에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Siemens SITRANS L 38 페이지. Ultrasonic transmitters
Siemens SITRANS L에 대해서도 마찬가지입니다: 적용 사례 (11 페이지)
6.4
20 mA calibration
6.5
Blanking
Blanking is used to ignore the zone in front of the transducer where false echoes are at a level
that interfere with the processing of the true echo. It is measured outward from the sensor
face. The minimum recommended blanking value is 0.25 m (0.82 ft) but can be increased in
order to extend the blanking.
①
②
SITRANS LU180
Operating Instructions, 09/2021, A5E37100674-AB
20 mA calibration initiated
view stored 20 mA calibration value
(i.e. 0.50 m)
press "4" to increase to new calibration value
(i.e. 0.45 m)
new calibration value
SITRANS LU180
Blanking
Operating
6.4 20 mA calibration
25