3.2
Cooling space for capacitors
Make sure that sufficient cooling space is provided:
• A minimum distance of 20 mm between the capacitors is necessary to maintain sufficient
cooling.
• Keep at least 20 mm space above the capacitor and do not attach any mounting components
at the crimp or on top. This gap will allow a longitudinal extension of the can in order to
ensure that the over-pressure disconnector can fully extend.
Note
The pictures depicted above are for illustration purposes only. Actual sample will be as per MLFB
type.
Using reactors: cooling space for cables
If reactors are used in an application, note that they operate at a much higher temperature. The
distance between the reactor and capacitor must be large enough so that no reactor heat is
conducted via the connection cable to the capacitor, or that heat radiation from the reactor to
the capacitor causes overheating.
Installation and maintenance instructions for Power Factor Correction (PFC) capacitors
Installation Manual, 05/2022, L1V30884033A
Mounting
3.2 Cooling space for capacitors