Siemens SIVACON 설치 매뉴얼 - 페이지 14

{카테고리_이름} Siemens SIVACON에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Siemens SIVACON 34 페이지. Distribution systems installation and maintenance instructions for power factor correction (pfc) capacitors

Siemens SIVACON 설치 매뉴얼
Mounting

3.3 Fixing threaded bottom stud

3.3
Fixing threaded bottom stud
The threaded mounting stud is at the bottom of the capacitor:
Fixing
The threaded bottom stud must be fastened with certain specified torques:
• PhaseCap, PhaseCap Compact, PhaseCap Energy +, PhaseCap HD, DeltaCap:
M12 bottom stud: torque 10 Nm.
• PhiCap:
M12 bottom stud for diameters > 53 mm: torque 10 Nm
M 8 bottom stud for diameters ± 53 mm: torque 4 Nm
14
Installation and maintenance instructions for Power Factor Correction (PFC) capacitors
Installation Manual, 05/2022, L1V30884033A