Mounting
3.3 Fixing threaded bottom stud
3.3
Fixing threaded bottom stud
The threaded mounting stud is at the bottom of the capacitor:
Fixing
The threaded bottom stud must be fastened with certain specified torques:
• PhaseCap, PhaseCap Compact, PhaseCap Energy +, PhaseCap HD, DeltaCap:
M12 bottom stud: torque 10 Nm.
• PhiCap:
M12 bottom stud for diameters > 53 mm: torque 10 Nm
M 8 bottom stud for diameters ± 53 mm: torque 4 Nm
14
Installation and maintenance instructions for Power Factor Correction (PFC) capacitors
Installation Manual, 05/2022, L1V30884033A