Cisco 2524 - Router - EN 설치 준비 - 페이지 5

{카테고리_이름} Cisco 2524 - Router - EN에 대한 설치 준비을 온라인으로 검색하거나 PDF를 다운로드하세요. Cisco 2524 - Router - EN 19 페이지. Troubleshooting guide
Cisco 2524 - Router - EN에 대해서도 마찬가지입니다: 구성 매뉴얼 (23 페이지), 구성 매뉴얼 (23 페이지), 개요 (10 페이지), 문제 해결 매뉴얼 (4 페이지)

Cisco 2524 - Router - EN 설치 준비

Configuring Equipment Racks

The following tips will help you plan an acceptable equipment rack configuration:
Enclosed racks must have adequate ventilation. Ensure that the rack is not overly
congested because each unit generates heat. An enclosed rack should have louvered
sides and a fan to provide cooling air.
When mounting a chassis in an open rack, ensure that the rack frame does not block the
intake or exhaust ports. If the chassis is installed on slides, check the position of the
chassis when it is seated all the way into the rack.
In an enclosed rack with a ventilation fan in the top, excessive heat generated by
equipment near the bottom of the rack can be drawn upward and into the intake ports of
the equipment above it in the rack. Ensure that you provide adequate ventilation for
equipment at the bottom of the rack.
Baffles can help to isolate exhaust air from intake air, which also helps to draw cooling
air through the chassis. The best placement of the baffles depends on the airflow patterns
in the rack, which are found by experimenting with different arrangements.

Power Supply Considerations

Check the power at your site to ensure that you are receiving "clean" power (free of spikes
and noise). Install a power conditioner if necessary.
Warning
versions of this warning, refer to the appendix "Translated Safety Warnings.")
The device is designed to work with TN power systems. (To see translated
Preparing to Install the Cisco 2524 and Cisco 2525 Routers 2-5
General Site Requirements