Rack-Mount the Chassis
Figure 2: Attach the Inner Rail to the Side of the Chassis
1
Front of chassis
3
M3X6mm screw (one per side)
Step 3
Open the front securing plate on both slide-rail assemblies. The front end of the slide-rail assembly has a spring-loaded
securing plate that must be open before you can insert the mounting pegs into the rack-post holes.
On the outside of the assembly, push the green arrow button toward the rear to open the securing plate.
Figure 3: Front Securing Mechanism Inside the Front End
1
Front mounting pegs
Works with square slots, 7.1 mm holes, and
Note
10-32 threaded holes
3
Rack post
Step 4
Install the slide rails into the rack:
a) Align one slide-rail assembly front end with the front rack-post holes that you want to use.
Rack-Mount the Chassis
4
2
Inner rail
2
Securing plate shown pulled back to open position
Rack-Mount the Chassis