You can use the base plate or extender base holes to route the fibers. Cisco recommends using the base
plate holes for the bottom node and the extender base holes for the other three nodes on the four-node
rack. All electrical cables will be routed in the back of the rack in the extender bases. Holes should
already be cut out in the raised floor tile to compensate for any DS1, DS3, ground and power cables.
Once all fiber cables have been placed in the front portion of the rack, replace the base plate by sliding
Step 3
it toward the back of the rack.
Figure 10
shows the routed fiber with the base plate replaced.
Figure 10
Raised Floor Base Fiber Routing
Unpacking and Installing the Cisco ONS 15454 Four-Shelf and Zero-Shelf Bay Assembly