10 . c
onnection examples
connection of Level meter HLM-35-C-I with current output to the unit
PDU-4xx-P (output 4 ... 20 mA) using junction box NB
In the case using a connection box with integrated overvoltage protection, the sensor
needs to be connected to the bottom series of terminals. This series of contacts is marked
by label SENSOR.
connection of Level meter HLM-35-C-U with voltage output to the unit
PDU-4xx-P (output 0 ... 10 V) using junction box NB
In the case using a connection box with integrated overvoltage protection, the sensor
needs to be connected to the bottom series of terminals. This series of contacts is marked
by label SENSOR.
connection of Level meter HLM-35-C-I with current output to the unit
PDU-4xx-W (output 4 ... 20 mA) using junction box NB
In the case using a connection box with integrated overvoltage protection, the sensor
needs to be connected to the bottom series of terminals. This series of contacts is marked
by label SENSOR.
10
cable shield
cable shield
cable shield
internally connected
cable shield
internally connected
cable shield
cable shield
internally connected
HLM–35