Dinel ULM-53L-10 사용 설명서 - 페이지 9
{카테고리_이름} Dinel ULM-53L-10에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Dinel ULM-53L-10 16 페이지. Ultrasonic level meters
![Dinel ULM-53L-10 사용 설명서](/uploads/products/server2/664655/664655.jpg)
k) The level meter must not be installed in places
with direct solar radiation and must be protected
against weather conditions.
l) In case the installation at places with direct solar
radiation is inevitable, it is necessary to mount
a shielding cover above the level meter (Fig. 8).
m) To lower the minimum distance to the medium meas-
ured, a reflection board made from solid, even and
smooth material can be installed together with the
level meter (Fig. 10). Subsequently, the tank can be
filled nearly up to the maximum volume. The solution
is suitable for open tanks and reservoirs.
n) Scattering or attenuation of the ultrasonic signal can
result if the surface level has been moderately stirred
or rippled as a consequence a stirrer's operation,
inflow of liquid and the like. Consequently, measuring
range or unreliable level meter's functioning might
follow (Fig. 11).
o) False surface reflections of the ultrasonic signal
might result as a consequence of rotating mixer's
blades that ripple the surface level and thus cause
unreliable level meter's functioning (Fig. 12).
p) The level meter should not be installed at places
where ultrasonic signal false reflections caused
by stirrer blades might occur (Fig. 13).
Fig. 10: Moderately stirred
surface
© Dinel, s.r.o.
ULM–53L
!
Fig. 11: Intensely stirred
surface
Fig. 8: Direct solar radiation shielding
cover
H + L = Dead zone
Fig. 9: Reflection board
!
Fig. 12: False reflection caused by
mixer blade
9