Connection procedure
1. Connect the network cables to connectors [X1] and [X2] on the module.
2. Connect the cable from the master to the left port [X1].
3. In the line topology, if there are more slave devices in the same line, connect the next slave device to
the right port [X2].
Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters.
See the appropriate drive manual.
Basic parameter settings
Index
Name
20.01
Ext1 commands
22.11
Speed ref1 source
28.11
Frequency ref1 source FBA A ref 1
50.01
FBA A enable
50.02
FBA A comm loss func Fault
51.02
Profile
To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par refresh.
Further information
See the latest version of FEPL-02 Ethernet POWERLINK
adapter module user's manual (3AUA0000123527
[English]) in ABB library (www.abb.com/drives/documents)
FEPL-02 manual
3AXD50000158164 Rev A (EN) 2017-11-23
Value
Fieldbus A
FBA A ref 1
Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.
The CANopen device profile (CiA 402) is the default value.
For more information on fieldbus options and protocols
provided by ABB Drives, see the fieldbus
communications web page
.
(new.abb.com/drives/connectivity/fieldbus-connectivity).
Fieldbus communications web page