Vizzyalarm™ 1-Zone WiFi Alarm Panel - Installation Instructions
Installation of the Alarm Panel
3. If connecting to an existing alarm security system or building automation system (BAS), use 18 gauge 2-conductor wire to
connect the existing product to the AUX inputs on the terminal block (Fig. 7). See below for wiring information. The
auxiliary contacts are activated when the sensor (signaling device) contacts are "closed" during an alarm condition
(normally open or normally closed). When connected, run the wire(s) towards the bottom/center of the alarm panel to go
through the wiring access hole once the enclosure cover is replaced (Fig. 9 and Fig. 10).
4. Connect the sensor (signaling device) to the ALARM inputs on the terminal block (Fig. 8). See below for wiring
information. The alarm is activated when any "dry" type sensor that "closes" during an alarm condition (normally open or
normally closed). When connected, run the wire(s) towards the bottom/center of the alarm panel to go through the wiring
access hole once the enclosure cover is replaced (Fig. 9 and Fig. 10).
Note: When installing a sensor or device, always refer to its installation instructions for complete operating information.
CAUTION: Route all wires away from sharp objects and internal components when installing wires.
Auxiliary Contacts:
Terminals AUX
Connects to external monitoring device
Normally Open; Single Pole, Single Throw
30VDC, 700mA maximum
Note: The auxiliary dry contacts of the alarm panel are normally open ONLY,
recommended to use 18 gauge 2-conductor wire. Used for remote monitoring.
Sensor/Signaling Device:
Terminals ALARM
Zone-1 Alarm
Normally Open or Normally Closed
3-10VAC/DC, 10mA minimum
Note: Use normally open sensors (signaling device) for high level alarm indication
and normally closed sensors (signaling device) for low level alarm indication.
5. After the wiring is completed and before replacing the enclosure cover, run the wire(s) towards the bottom/center of the
alarm panel to go through the wiring access hole once the enclosure cover is replaced (Fig. 9 and Fig. 10).
CAUTION: Route all wires away from sharp objects and internal components when installing wires.
Alderon Industries, LLC - Leading Edge Control Products | 218.483.3034 | [email protected] | [email protected] | alderonind.com
(continued)
(Fig. 9)
(Fig. 7; auxiliary contacts)
(BAS)
(Fig. 8; sensor/signaling device)
(Fig. 10)
Installation Instructions | Page 3