Alderon Industries Check It Panel 운영, 유지보수 및 설치 매뉴얼 - 페이지 6

{카테고리_이름} Alderon Industries Check It Panel에 대한 운영, 유지보수 및 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Alderon Industries Check It Panel 6 페이지. 1 phase simplex demand dose

Check It Panel
1 Phase Simplex Demand Dose
Operation, Maintenance & Installation Manual
Check It Panel Self Diagnosing Instructions:
#4. Using the Check It feature to troubleshoot your control panel.
Fig #1.
Fig #2.
Fig #2A.
Illustration (Fig#3A) shows the Stop float is activated,
but the indicator light on th ecommand center in
(Fig#2A) is not illuminated. The Stop float is not
working properly and should be replaced.
Alarm Float
Start Float is activated
Stop Float is activated
TM
Place the HOA (Hand-Off-Auto) switch into the
Run indicator light will illuminate and turn on the pump.
If the HOA (Hand-Off-Auto) switch is in the
cally checking the true status of the floats. EXAMPLE: Fig#2. The green pump run light is
illuminated because the HOA switch is in the hand mode.
EXAMPLE: Fig#2A.
The Start float indicator
indicator is illuminated.
The Stop float indicator
light is not.
(Hand) position you will be automati-
Fig #2B.
.
However, the example below (Fig#3B) shows that the
same float is not working, but for a different reason. In
this example the float is hung up in the tank.
Stop Float is NOT activated
(Hand) position. The Pump
EXAMPLE: Fig#2B. The same
indicator lights are illuminated.
The Start float indicator
is illuminated.
The Stop float indicator
light is not.
Alarm Float
Start Float is activated
P/N L1153
Page 6 of 6