eControls Comfort365 C365T11 설치 프로그램 및 사용자 설명서 - 페이지 6
{카테고리_이름} eControls Comfort365 C365T11에 대한 설치 프로그램 및 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. eControls Comfort365 C365T11 13 페이지.
eControls Comfort365 C365T11에 대해서도 마찬가지입니다: 사용자 설명서 (4 페이지), 설치 프로그램 및 사용자 설명서 (13 페이지), 사용자 설명서 (4 페이지), 설치 프로그램 및 사용자 설명서 (13 페이지), 설치 프로그램 및 사용자 설명서 (13 페이지), 설치 (2 페이지)
04 Compressor Minimum Off Time
Use the
UP/DOWN
keys to
change the minimum off time
(minutes) before restarting the
compressor.
Touch
NEXT
or
ENTER.
Factory Default: 2 Minutes. Range: 0 to 9 Minutes
05 Heating Minimum Off Time
Use the
UP/DOWN
keys to
change the minimum off time
(minutes) before restarting a
gas furnace or electric strip
heater.
Touch NEXT or ENTER.
Factory Default: 0 Minutes. Range: 0 to 9 Minutes
06 Minimum Run Time
Use the
UP/DOWN
keys to
change the minimum run time
(minutes) before turning a
system off.
Touch NEXT or ENTER.
Factory Default: 2 Minutes. Range: 0 to 9 Minutes
07 Setting On-Off Temp Differential
Use the
UP/DOWN
keys to
select 0, 1, 2.
Touch NEXT or ENTER.
o
Differential Mode0
0.5 F On/Off span.
o
Differential Mode1
1.0 F On/Off span.
o
Differential Mode2
1.5 F On/Off span.
08 Smart Recovery
Smart recovery initiates a heating or cooling call so that the space is
at temperature when the setback period ends.
Use the
UP
key to select ON to
turn on smart recovery or the
DOWN
key to select OF to turn
smart recovery off.
Touch
NEXT
or
ENTER
.
Option
NEXT
ENTER
Option
NEXT
ENTER
Option
NEXT
ENTER
Option
NEXT
ENTER
Factory Default: #1. Range: 0, 1 or 2.
Option
NEXT
ENTER
Factory Default: Off. Range: On or Off.
09 Vacant Heating Setpoint
Use the
UP/DOWN
keys to
select the heating temperature
when the space is vacant.
Touch NEXT or ENTER.
10 Vacant Cooling Setpoint
Use the
UP/DOWN
keys to
select the cooling temperature
when the space is vacant.
Touch NEXT or ENTER.
11 Calibrate Living Area Temperature Sensor
Use the
UP/DOWN
keys to
change the Living area
temperature to the temperature
that the user feels is correct.
Touch NEXT or ENTER.
12 Calibrate Sleeping Area Temperature Sensor
Use the UP/DOWN keys to
change the Sleeping area
temperature to the temperature
that the user feels is correct.
Touch NEXT or ENTER.
13 Airflow Update Time
This is the frequency, in minutes, that the damper position is updated.
Use the
UP/DOWN
keys to set
the time in minutes to update
the sleeping and living area
airflow.
Touch NEXT or ENTER.
Factory Default: 2 Minutes. Range: 1 to 20 Minutes.
6
Option
Heat
Vacant
NEXT
ENTER
o
o
Factory Default: 65 F.
Range: 44 F to 75 F
Option
Cool
Vacant
NEXT
ENTER
o
o
Factory Default: 80 F.
Range: 74 F to 95 F
Option
Living
NEXT
ENTER
Factory Default: None.
Range - +/-5
Option
Sleeping
NEXT
ENTER
Factory Default: None.
Range - +/-5
Option
NEXT
ENTER
o
o
o
o