Installer menu
11 Filter Alarm interval
12 Working Hours Counter
13 Save settings
14 Load settings
15 Restore Default Settings
Installer menu
11 Filter Alarm interval
12 Working Hours Counter
13 Save settings
14 Load settings
15 Restore Default Settings
Installer menu
16 Contrast
17 Debug page
Installer menu
16 Contrast
17 Debug page

7.3 Additional functionalities

SLAVE MODE
In case the SLAVE jumper (Fig. 5.g - JP2) is short-circuited before powering the unit, the unit works in SLAVE MODE; the
operating speed is determined by the 1-10V signal received at the SLAVE input. All the operating logics described in the Mode
selection are ignored (paragraph 7.1).
BYPASS
The QR590E is equipped with a physical bypass which allows to mitigate the heat exchange when the indoor and outdoor
temperature combinations are such that the heat exchange is not recommended. In this case the Bypass icon
on the LCD.
The parameters "Desired Temperature", "Tmax Free Heating", "Tmin Free Cooling" (Installer Menu 4) are to be meant as follows:
"Desired Temperature" is the ambient temperature desired by the user
"Tmax Free Heating" is the maximum outside temperature allowed for free heating operation
"Tmin Free Cooling" is the minimum outside temperature allowed for free cooling operation.
FAULT HANDLING
Code error description (Fig. 7.b - )
E000 no RS485 connection
E001 no rotation of the exhaust air fan (Fig. 8.a - )
E002 no rotation of the intake air fan (Fig. 8.a - )
E003 thermistor T11 broken/disconnected (Fig. 7.a)
E004 thermistor T12 broken/disconnected (Fig. 7.a)
E005 thermistor T21 broken/disconnected (Fig. 7.a)
E006 thermistor T22 broken/disconnected (Fig. 7.a)
E007 dehumidifier alarm (BST INPUT)
E008 CTRL-DSP internal error
NOTE: the controller board verifies the presence of CTRL-DSP periodically; if CTRL-DSP is absent (or faulty), the unit works in 3V
mode at speed 1 (DEFAULT condition).
ANTI-FROST
Intake Fan speed is reduced during very cold weather in order to prevent ice inside the unit which could damage the heat
exchanger.
In this case the ANTI-FROST icon
14
It allows to load the saved setting on the next unit.
Press OK to enter.
Use  or  to choose the desiderd saved setting.
Press OK to select.
Press OK to confirm.
Press ESC to go back to the previous menu.
It allows to restore all the factory settings (DEFAULT).
Press OK to enter.
Press OK to confirm.
It allows to set the LCD contrast.
Press OK to enter.
Use  or  to increase or decrease the contrast.
Press OK to confirm.
It shows the internal functional parameters of the unit.
Press OK to enter.
Press ESC to go back to the previous menu.
R
7
6
is activated on the LCD.
is activated