ABB REF601 제품 설명서 - 페이지 14

{카테고리_이름} ABB REF601에 대한 제품 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB REF601 20 페이지.

ABB REF601 제품 설명서
Feeder Protection
REF601 IEC
Product Version: 1.0
Magnetic immunity tests
Power-Frequency
Magnetic Field
Pulse Magnetic Field
Electrical Insulation and mechanical construction tests
Make and carry
Breaking capacity for
d.c., L/R ≤ 40 ms
Make and Break capacity
for resistive load
Mechanical durability
Safety tests
Protective Bonding Re-
sistance
14
IEC 61000-4-8
Level 5, X-Y-Z axis :
-100A/m continuously
-1000A/m short time
IEC 61000-4-9
Level 5, 5 positive and 5 negative, 8/20μs
pulses every 10s:- 1000 A/m
IEC 60255-23
Signaling : 10A@24VDC for 0.5s
(Replaced by
and 8A@24VDC for 3s
IEC61810-2, Ed.1.0)
Tripping : 30A@24V DC for 0.5S
and 15A@24VDC for 3S
IEC 60255-23
Signaling: 0.15A@220VDC and 4.5A @30VDC
Tripping: 0.2A@220VDC and 5.5A@35VDC
IEC 60255-23
Signaling: 6A @240V ac
Tripping: 8A@240V ac
IEC 60255-6
10,000 operations ; tripping and signaling
contacts
IEC 60255-27
ABB