ABB REF601 Manual do produto - Página 14

Procurar online ou descarregar pdf Manual do produto para Dispositivo de proteção ABB REF601. ABB REF601 20 páginas.

ABB REF601 Manual do produto
Feeder Protection
REF601 IEC
Product Version: 1.0
Magnetic immunity tests
Power-Frequency
Magnetic Field
Pulse Magnetic Field
Electrical Insulation and mechanical construction tests
Make and carry
Breaking capacity for
d.c., L/R ≤ 40 ms
Make and Break capacity
for resistive load
Mechanical durability
Safety tests
Protective Bonding Re-
sistance
14
IEC 61000-4-8
Level 5, X-Y-Z axis :
-100A/m continuously
-1000A/m short time
IEC 61000-4-9
Level 5, 5 positive and 5 negative, 8/20μs
pulses every 10s:- 1000 A/m
IEC 60255-23
Signaling : 10A@24VDC for 0.5s
(Replaced by
and 8A@24VDC for 3s
IEC61810-2, Ed.1.0)
Tripping : 30A@24V DC for 0.5S
and 15A@24VDC for 3S
IEC 60255-23
Signaling: 0.15A@220VDC and 4.5A @30VDC
Tripping: 0.2A@220VDC and 5.5A@35VDC
IEC 60255-23
Signaling: 6A @240V ac
Tripping: 8A@240V ac
IEC 60255-6
10,000 operations ; tripping and signaling
contacts
IEC 60255-27
ABB