Feeder Protection
REF601 IEC
Product Version: 1.0
Environmental tests
Shock test
Bump test
Electrical Insulation and mechanical construction tests
Power-Frequency with-
stand Voltage (Insulation
test voltage)
Lightening Impulse Volt-
age
Insulation resistance
Electromagnetic Compatibility Tests
Emission Test (For test
site measurements,)
Power supply Emission
Conducted Immunity and Power unit tests
Electrostatic Discharge
Fast Low Energy Tran-
sient (EFT) (Including
functional earth port)
12
IEC60255-21-2
Shock response test:
(based on IEC60068-
Class2. Peak acceleration (A) 10gn,
2-27 test Ea and
Duration of the pulse (D) 11ms,
IEC60068-2-29 test
3 pulses in each direction
Eb)
Shock withstand test:
Class2. Peak acceleration (A) 30gn,
Duration of the pulse (D) 11ms,
3 pulses in each direction
IEC60255-21-2
Class2. Peak acceleration (A) 20gn,
(based on IEC60068-
Duration of the pulse (D) 16ms,
2-27 test Ea and
1000 pulses in each direction
IEC60068-2-29 test
Eb)
IEC 60255-5
Level 2, 50Hz, 1min:- 2 kVrms (CM)
IEC 60255-5
Level 3, 1.2/50μs, 500Ω, source Z,
0.5J source energy, - 5kVp (CM )
IEC 60255-5
500Vdc (CM) test voltage: >100MΩ
IEC 60255-25
30...230MHz:
40dB (μV/m) quasi peak at 10m distance
230...1000MHz:
47dB (μV/m) quasi peak at 10m distance
IEC 60255-25
0.15...0.5MHz:
79dB (μV/m) quasi peak
66dB (μV/m) average
0.5...30MHz:
73dB (μV/m) quasi peak
60dB (μV/m) average
IEC 60255-22-2
Level 3, 5/30ns pulse, 5 discharges:
±6kVp contact
±8kVp air
IEC 60255-22-4
5/50ns pulse, 2.5 kHz, ±4kVp,
ABB