ABB REF601 Manual do produto - Página 10

Procurar online ou descarregar pdf Manual do produto para Dispositivo de proteção ABB REF601. ABB REF601 20 páginas.

ABB REF601 Manual do produto
Feeder Protection
REF601 IEC
Product Version: 1.0
Non-directional earth-fault protection
Low-set stage Io >
Nominal value of earth current
Measurement range
Setting range for External earth
fault measurement
Setting range for Internal earth
fault measurement
Setting range of time multipler
' k '
Operate time at DT mode to >
Inverse time characteristics
Accuracy of pick-up current
Accuracy of operate time :
DMT and RI characteristic
IDMT characteristic
DMT and RI characteristic
IDMT characteristic
Reset ratio
High-set stage
Setting range
Io >>
Operation mode
Operate time to >>
Accuracy of pick-up current
Accuracy of operate time
Reset ratio
Transformer inrush detection
Inrush threshold value
Ratio Setting
10
1 A
0.05...5 x In
0.05...1 x In in step of 0.05, infinite
0.20...1 x In in step of 0.05, infinite
0.1...1.6, in step of 0.1
0.1...1.6 sec insteps of 0.1 for B=1
0.5...8.0 sec insteps of 0.5 for B=5
IEC 60255-3:
Normal inverse, Extremely inverse,
Very inverse, Long time inverse
Special curves:
RI inverse time
± 5% of set value for ext. measurement
± 15% of set value for int. measurement
For external measurement
± 5% of set value or ± 30 msec
class E(5) or ± 30 msec
For internal measurement
± 10% of set value or ± 30 msec
class E(7.5) or ± 30 msec
IDMT : 0.96 and DMT : 0.98
0.5...4.0 x In in step of 0.25, infinite
Definite time
0.00...0.75 in step of 0.05
± 5% of set value for ext. measurement
± 15% of set value for int. measurement
± 5% of set value or ± 30 msec
for int. measurement,
± 10% of set value or ± 30 msec
for ext. measurement
Note : 45 msec for setting of 0.00 msec
0.98
0.2...20 x In
30%...50%
ABB