DISCOVER 950-0025 사용자 설명서 - 페이지 11
{카테고리_이름} DISCOVER 950-0025에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. DISCOVER 950-0025 18 페이지. Sma sunny island
5. INSTALLING AND CONNECTING LYNK II TO THE SMA NETWORK
5.1 Networking Discover Lithium Batteries with LYNK II Gateway
• Turn OFF all devices before connecting cables.
• Do not plug an AEbus or LYNK RJ45 network cable or terminator into the 10/100
Ethernet port of the LYNK II.
• Do not connect a CAT5 cable from the AEbus, LYNK, or Ethernet ports of the LYNK II
to a WAN or MODEM port of a network router.
• Mixing the LYNK Network with other networks may result in equipment malfunction
and damage.
• Unless specified by Discover Battery, do not connect power electronics directly to the
LYNK network or AEbus network.
Refer to the LYNK II Installation and Operation Manual (805-0033) for instructions
on network layouts, connections, and termination of compatible Discover Lithium
battery models. Some key points are repeated here for convenience.
• Connect at least one battery to the LYNK Port on the LYNK II Communication
Gateway.
• A network of batteries will communicate as one battery.
• Connect no more than one network of batteries to the LYNK II.
• Proper system function requires network termination – some batteries and
devices may auto-terminate.
• LYNK II requires power from one of three available sources (13-90 VDC power
supply, a USB device, or AEbus Port or LYNK Port enabled Discover Lithium
battery).
• Discover Lithium batteries must be set to ON to supply power and communicate
with LYNK II.
LYNK II is internally terminated. AES batteries are not internally terminated. When
using LYNK II with an AEbus network, install a terminator at the end opposite LYNK
II.
NOTICE
NOTICE
11
Figure 3. AES