Distech Controls GS-CDR02K 하드웨어 설치 매뉴얼 - 페이지 3

{카테고리_이름} Distech Controls GS-CDR02K에 대한 하드웨어 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Distech Controls GS-CDR02K 9 페이지. Room carbon dioxide transmitter

Mount the base by screwing to an electrical box or directly to the wall as shown in Figure 5.
Figure 5. Mounting base to electrical box
After the base is screwed to an electrical box or directly to the wall using the appropriate holes, remove the PCB from the anti-static
bag, feed connection wires through the center hole and place the top of the PCB into the PCB holders on the backplate and snap the
bottom of the PCB into place as shown in Figure 5.
Making wiring connections as per the Wiring Illustrations and install the decorative cover by placing the top of the cover into the cover
holder on the top of the backplate and snapping the bottom into place as shown in Figure 5. Tighten the security screw with a Phillips
screwdriver.
Wiring
Figure 6. GS-CDR02K PCB
Deactivate the power supply until all connections are made to the device to prevent electrical shock or equipment damage. Use 16-
22 AWG shielded wire for all connections (only ground the shield at the controller end) and do not locate the device wires in the same
conduit with wiring used to supply inductive loads such as motors. Pull at least six inches of wire into the enclosure and complete the
wiring connection according to the wiring diagram. Figure 7.
Figure 7. Wiring diagram
3/9