This is a 3-wire sourcing device. Connect the plus DC or the AC voltage hot side to the PWR terminal and the common is connected
to the COM terminal. The device is reverse voltage protected and will not operate if connected backwards. It has a half-wave power
supply so the supply common is the same as the signal common. Several devices may be connected to one power supply and the
output signals all share the same common. Use caution when grounding the secondary of a transformer or when wiring multiple
devices to ensure the ground point is the same on all devices and the controller.
The CO
analog output is available on the CO
2
10 Vdc) see Figure 8 and connects to the controller analog input. Check the controller Analog Input to determine the proper connection
before applying power. Both current and voltage signals are referenced to the COM terminal. The current output operates in the active
mode and does not require a loop power supply (the signal current is generated by the transmitter and must not be connected to a
powered input or device damage will result).
The optional relay output connects to the RELAY terminals. The relay output is completely isolated and has a Normally Open (NO)
signal. This signal can be used to directly control an alarm or ventilation fan. See specifications for contact ratings. See Figure 9.
The optional override signal is a two-wire dry contact normally open switch connected to the SWITCH terminals. See Figure 10.
The optional setpoint signal is a resistive signal that can vary from 0-10K ohms (for example) to simulate a slidepot action. It is available
on the SETPNT terminal and is referenced to COM. Several resistive values are available and the operation may be configured as
normal or reverse acting via the Setup Menu. See Figure 10.
The optional two-wire temperature sensor output is available with various RTDs and thermistors to suit all control applications and is
available on the TEMP terminals. See Figure 10.
Outputs
The CO
output signal is scaled such that 4-20 mA (or 0-5 / 0-10 Vdc) equals 0-2000 ppm by default. The signal span may be changed
2
via the Setup Menu from 1000 to 10,000 ppm in 500 ppm increments.
Start-up Mode
Verify the device is properly wired and connections are tight. Ensure the mA / VOLT switch is set for the correct signal type. Apply
power and the LCD will indicate the software version number, the output signal type and then the sensor will begin a one-minute
warm-up countdown. When the warm-up time expires the device will enter normal mode.
4/9
terminal. This signal is switch selectable for either 4-20 mA or voltage output (0-5 / 0-
2
Figure 8. Analog output switch
Figure 9. Optional relay output wiring
Figure 10. Optional signal wiring