Operating Instructions
Transducer for AC current SINEAX I 552
Safety precautions to be strictly observed are marked
with following symbols in the Operating Instructions:
Contents
1. Read first and then ... ................................................. 9
2. Brief description ......................................................... 9
3. Technical data ............................................................ 9
4. Mounting ................................................................... 9
5. Electrical connections ............................................... 10
7. Commissioning and maintenance ............................ 11
8. Releasing the transducer .......................................... 11
9. Instruments admissions ............................................ 11
10. Dimensional drawing ................................................ 12

1. Read first and then ...

The proper and safe operation of the device
assumes that the Operating Instructions is
read carefully and the safety warnings given
in the various Sections

4. Mounting

5. Electrical connections
6. Adjustable measuring range
by DC calibration
are observed.
The device should only be handled by appropriately
trained personnel who are familiar with it and authorised
to work in electrical installations.

2. Brief description

The SINEAX I 552 measuring transducer is used to convert a
sine-wave or distorted AC current.
The output signal, in the form of a load independent DC
current or voltage, is proportional to the measured value.

3. Technical data

Measuring input
Nominal frequency:
50/60 or 400 Hz
Nominal input current: 0 - 0.1/0.5 to 0 - 1.2/6 A
Measuring output
DC current:
0(0.2) - 1 to 0(4) - 20 mA
Burden voltage:
15 V
max. [kΩ] ≤
External resistance:
R
ext
I
= Full output value
AN
DC voltage:
0(0.2) - 1 to 0(2) - 10 V
min. [kΩ] ≥
External resistance:
R
ext
Response time:
50 or 300 ms
Power supply
AC/DC power pack (DC or 40 - 400 Hz)
Rated voltage
85 - 230 V DC / AC
24 - 60 V DC / AC

≤ 1.5 W resp. ≤ 3 VA

Power consumption:
Option:
Connected to the low tension ter-
minal side 12 and 13 see Figs. 4
and 5
24 V AC or 24 - 60 V DC
Accuracy (acc. to IEC 688)
Reference value:
Output end value
Basic accuracy:
Class 0.5
Safety
Pollution degree:
2
Installation category:
III
Environmental conditions
Operating temperature: - 10 to + 55 °C
- 40 to + 70 °C
Storage temperature:
Relative humidity of
≤ 75%
annual mean:
6. Mounting
The SINEAX I 552 can be mounted on a top-hat rail.
Note "Environmental conditions" in Section
"3. Technical data" when determining the place
of installation!
Simply clip the device onto the top-hat rail (EN 50 022) (see
Fig. 1).
Fig. 1. Mounting onto top-hat rail 35 × 15 or 35 × 7.5 mm.
15 V
I
[mA]
AN
U
[V]
A
2 mA
Tolerance
DC - 15 to + 33%
AC ± 15%