Internal clock (RTC)
Function:
Time reference, Counter for opera-
ting hours
Accuracy:
± 2 Minutes/Month (15 till 30°C)
trimmable via PC-Software
Synchronization via:
Measurement input,
HV-Input 110/230 V AC,
Synchronization pulse (digital in-
put)
Running reserve:
> 10 years
Response time
The total response time is the addition of the measurement
time t
of the input quantities and the processing time t
1
the respective output (analog output, bus, digital output,
relay).
Meas. time t 1
Processing time t 2
Input quantities
Analog output
Modbus, USB
Limit
monitoring
Measurement time t
1
Basic measurement quantities
Measurement interval:
programmable, 1 .. 999 periods
(Averaging time RMS value)
Measurement time t
:
2 x measurement interval
1
+ 17ms
System analysis quantities
Measurement interval:
18 periods
Measurement time t
:
2 x measurement interval
1
Analog input
Measurement time t
:
25 ms .. 30 s (programmable)
1
Digital input
Measurement time t
:
< 25 ms
1
HV-Input 110/230 V AC
Measurement time t
2 till 255 periods (programmable)
1
Total response time t
+ t
1
Analog output:
t1 + 10 ms .. 60 s,
programmable
Modbus / USB:
t1
Digital output:
t1 + 8 ms + Logic module
Relay:
t1 + 30 ms + Logic module
(Logic module: Switch-in/dropout delay 0...65 s, program-
mable)
Example: Relay has to toggle if P > P
50 Hz, Averaging time is 1 period, switch-in delay
logic set to 0 s
Logic
Digital
module
output
Relay
2
, rated frequency is
limit
Response time 40ms + 17ms + 0ms + 30ms = 87ms
Ambient conditions, general information
Operating temperature: – 10 till 15 till 30 till 55 °C
Storage temperature:
Relative humidity:
Variations due to
ambient temperature:
Long term drift:
Altitude:
Others:
for
2
Mechanical attributes
Dimensions:
t
Mounting:
Orientation:
Housing material:
Flammability class:
Weight:
Security
The current inputs are galvanically isolated from each
other.
Protection class:
Pollution degree:
Enclosure protection:
Measurement category: CAT III (at ≤ 300 V versus earth)
Rated voltage
(versus earth):

7.5 Logger and lists (optional)

By means of these options measurements and events may be
long-term recorded. Depending on the application 7 different
kinds of data may be acquisited:
– Progression of mean-values with interval time t1
(1s...60min)
– Progression of mean-values with interval time t2
(1s ... 60min)
– Min/Max values during interval t3 (1s ... 3h)
– Meter readings
– List entries of alarms
– List entries of events
– List entries of system messages
They share the available storage space of 64Mb size. The
memory allocation may be performed using the CB-Manager
– 25 till + 70 °C
< 95% no condensation
0.5x Basic accuracy per 10 K
0.2x Basic accuracy per year
≤ 2000 m max.
Usage group II
acc. IEC / EN 60 688
186 x 90 x 62 mm
On top-hat rail acc.
DIN EN 50 022 (35 x 15 mm and
35 x 7.5 mm)
Any
Polycarbonat (Makrolon)
V-0 acc. UL 94, self-extinguishing,
non-dripping, free of halogen
500 g
II (protective insulation, voltage
inputs via protective impedance)
2
IP 40, housing
(test wire, IEC/EN 60 529
IP 20, terminals
(test fi nger, IEC/EN 60 529)
CAT II (at > 300 V versus earth)
Power supply: 265 V AC
Relay:
250 V AC
I/O's:
30 V DC
264 V AC(HV-Input)
11