ALTUS Du350 제품 설명서 - 페이지 10

{카테고리_이름} ALTUS Du350에 대한 제품 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. ALTUS Du350 18 페이지.

Duo Series
Doc. Code: CE113100
Voltage mode
Precision
Crosstalk DC @ 100 Hz
Output impedance
Minimum load impedance
Short circuit protection
Updating time
Stabilization time
Scale
Scale clearance
Over load indication
Notes
Updating time: maximum time between the end of cycle and the output updating.
Stabilization time: maximum time for output signal stabilization with a resistive load greater than or equal to 600 .
Counting: the scale limit may be modified by software, the maximum value is 30000.
Scale clearance: scale clearance allows DA to reaches voltage values out of range to compensate eventual offset errors of the
device to be controlled by the analog output.
Current Mode
Precision
Crosstalk DC at 100 Hz
Maximum load impedance
Updating time
Stabilization time
Scale
Scale clearance
Open loop indication
Notes
Updating time: maximum time between the end of cycle and the output updating.
Stabilization time: maximum time for output signal stabilization with a resistive load lower than or equal to 600 .
Counting: the scale limit may be modified by software, the maximum value is 30000.
Scale clearance: scale clearance allows DA to reaches voltage values out of range to compensate eventual offset errors of the
device to be controlled by the analog output.
Altus S. A.
DU350, DU351
 0.3% of scale limit @ 25°C
0.015% / ºC of scale limit
- 30 dB
22 
600 
Yes
1 ms
4 ms
Range
Counting
0 – 10 V
0 to 30.000
4 %
Yes (typically loads with impedance lower than 500 )
DU350, DU351
 0.3% of scale limit @ 25°C
0.015% / ºC of scale limit
- 30 dB
600 
1 ms
4 ms
Range
Counting
0 – 20 mA
0 to 30.000
4 %
Yes (typically loads with impedance greater than 650 )
DU350, DU351
Revision: G
Resolution
2.59 mV
Minimum Resolution
5.2 A
10