ALTUS Du350 제품 설명서 - 페이지 9
{카테고리_이름} ALTUS Du350에 대한 제품 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. ALTUS Du350 18 페이지.
Duo Series
Doc. Code: CE113100
Current Mode
Precision
Crosstalk DC @ 100 Hz
Input impedance
Maximum/minimum continuous
current without damage
Filtering
Scale
Diagnostic
Scale clearance
Notes
Filtering: the time constant value can vary 10% of its nominal value. The maximum deviation of the time constant value is equal
to the sampling rate. Ex: selecting the constant time equal to 1 s, the maximum time for the current value with filter to have 63%
of the input value is: 1 s * 110% + 60 ms = 1.16 s. The "Disabled" option is available as of version 1.11 of the MT8200.
Counting: the scale limit may be modified by software, the maximum value is 30000.
Scale clearance: defines the percentage over limit scale that can be read by analog inputs. This characteristic can be used to
compensate possible calibration errors of a used sensor.
Analog Output
Number of inputs
Output type
Conversion resolution
Terminal block configuration
Protection
Configurable parameters
Altus S. A.
DU350, DU351
0.3% of scale limit @ 25°C
0.015% / ºC of the limit scale
- 30 dB
124.5
25 mA / -2 mA
Configurable time constant:
Disabled, 2 ms, 90 ms, 1 s or 15 s
Range
Counting
0 – 20 mA
0 to 30.000
4 – 20 mA
0 to 30.000
Current below 3.8 mA (valid only with 4 - 20 mA scale; used to
indicate an open circuit)
4 %
DU350, DU351
2 non insulated (of logical circuit) analog outputs
Voltage: 0 to 10 Vdc
Current: 0 to 20 mA
12 bits
C3 –common for AO0 output
AO0 – analog output 0 (configurable by software as voltage or
current)
C4 – common for AO1 output
AO1 – analog output 1 (configurable by software as voltage or
current)
TVS diode in all analog outputs
Type of signal on each channel (voltage or current)
Scale limit per channel, maximum 30000
DU350, DU351
Revision: G
Sensitivity
5.1 A
5.1 A
9