(1)What type of system terminals are used in the heating circuit?
Reply
The unit is a cooling only model
Radiant panels (Floor, etc....)
Fan coils or low temperature radiators
Other applications
(2) Is the remote panel accessory installed (PR3) ?
Reply
Not installed
Installed
(3) Is the production of DHW envisioned?
Reply
Not envisioned
Envisioned
(4) Is a 3‐way diverter valve envisioned in the DHW production circuit?
Reply
Not envisioned
Envisioned
(5) Is a room thermostat installed?
Reply
Not installed
Installed
.
10
Operations to be performed
Go to question 2
Set the parameter StC (index 3 USER menu) with the value of 35 C
Set the parameter StC (index 3 USER menu) with the value of 45°C(default
value)
Set the parameter StC (index 3 USER menu) with the value of 55 °C
Operations to be performed
Go to question 3
Set the parameter PAN (index 9 INSTALLER menu) with the appropriate value,
selecting from:
Value (1):
• Season control piloted from the circuit board
• ON/OFF control enabled from PR3
Value (2):
• Season control enabled from PR3
• ON/OFF control from panel on machine
Value (3):
• Season control enabled from PR3
• ON/OFF control enabled from PR3
Operations to be performed
Go to question 5
Set the parameter ASA (index A INSTALLER MENU) with the value (1)
Operations to be performed
Go to question 5
Set the parameter AAS (index C INSTALLER menu) with the appropriate value
(in seconds). This parameter indicates the stand‐by tome for inversion
of the 3‐way diverter valve on the DHW
Operations to be performed
No operation
This parameter enables a digital clamp ID (indicated on the circuit board with
the code TRA) to which a room thermostat must be connected, used to disable
the compressors and the integrative resistances. Set the parameter trA (index
D INSTALLER menu), with the appropriate value, selecting from:
Value (1 or 2): Clamp ENABLED
Value (0 or 3): Clamp DISABLED
Remember that the OPEN state on the clamp represents:
• the compressors and resistances block function if the parameter is set at 1
• the compressors, pumps and resistances block function if the parameter is
set at 2
• represents the pump alarm (as in the previous software version), if the pa‐
rameter is set at the value 3
production system