Adjust heat < > vent differential (8)
Press the
to set the desired
temperature differential (dead band)
between heat and vent when in the Auto
mode.
Adjust GM 44 differential (9)
Press the
to set the number of degrees
that the 0 - 5VDC proportional band is to
vary over.
Adjust AmbiTec Plus type (10)
Press the
to set the control panel to
the type of unit required. If the control
panel is to be used to control an individual
heater then set the display to read, 'Adjust
Energy mizor 00' . If more than one control
panel is to be used to control the heaters in
a Master/Slave configuration the use the
to set the unit to be designated as the
Master to read 'Adjust Master 00' . If a unit
is to be designated as a slave panel then use
the
to set each slave to read 'Adjust
Slave XX' . XX is to be interpreted to be any
number from 01 - 31. No two-slave panels
are allowed to have the same number
assigned. Only one Master panel is allowed
on any one system.
Adjust reset (11)
Use the
to set the AmbiTec Plus to the
type of reset required. Type 01 is all relays
off and is used for those heaters with
automatic ignition where power to the
burner must be interrupted to cause burner
reset in case of burner lock out. Type 02 is
for use where a live or neutral is required to
be switched back to the heater unit to cause
burner reset.
Adjust V3 (12)
Use the
to change operation from
manual 'Vent' mode to V1 auto temperature
sensitive mode.
Adjust high fire time (13)
Use the
to set the time required for the
burner to be on high fire during light up for
proper ignition of the burner. The setting
may be from 00 - 99 seconds.
4
PLUS
ENERGY SAVING ELECTRONIC CONTROL PANEL
Adjust preheat mode (14)
Press the
to remain fixed at the time set in the adjust
preheat screen. Select 02 to allow the
controller to hold off the preheat to take
into account the actual ambient
temperature.
Adjust pre heat (15)
Use the
time from 0 hours to 4 hours in 30 minute
steps. Ideally this should be set to the time
it takes to raise the room temperature to
20˚C. Every on time will be advanced by
this preheat time.
Adjust day temperature band (16)
Use the
the
to set these to the lower end of the
range over which the day temperature may
be set in the normal display adjust screen.
Use the
to set the upper end of the range over
which the day temperature may be set in
the normal display adjust screen. The From
is adjustable from 00˚C to 50˚C and the To
is adjustable from 00˚C to 50˚C. However
the To reading can never be set lower than
the From reading.
Night temperature band (17)
Use the
the
to set these to set the lower end of
the range over which the day temperature
may be set in the normal display adjust
screen. Use the
Use the
range over which the day temperature may
be set in the normal display adjust screen.
The From is adjustable from 00˚C to 40˚C
and the To is adjustable from 00˚C to 50˚C.
However to To reading can never be set
lower than the From reading.
FWD clock 1 hour at 01:00 (18)
Use the
and the
to select the date position and the
to set the correct date for automatic clock
forward time.
to select 01 if the preheat is
to set the required preheat
to select 'From' reading. Use
to select To reading. Use the
to select From reading. Use
to select To reading.
to set the upper end of the
to move to the month position
to select the month. Use the
RTD clock 1 hour at 01:00 (19)
Use the
to move to the month position
and the
to select the month. Use the
to select the date position and the
to set the correct date for automatic
clock retard time.
Holiday (Covered only for frost
protection no night set back) (20)
Use the
to select the From date
position for the holiday period to start and
the
to set the date. Use the
select the From month position and the
to set the month. Use the
To date position for the holiday period to
end and the
to set the date. Use the
to select the To month position and the
to set the month.
Note If set the will turn off on the last OFF of
the From date and will turn back on again on
the first On of the To date.
Holiday 2 (21)
If required set a second holiday period as in
holiday 1.
Holiday 3 (22)
If required set a third holiday period as in
holiday 1.
Holiday 4 (23)
If required set a fourth holiday period as in
holiday 1.
Adjust Hand (24)
Use the
to adjust from 30 min. to 2
hours in 30 min steps.
to