Network connection
The configuration and use of the voice control interface
requires a connection to the home or company network.
The default IP address of the interface is: 192.168.0.110.
For the initial configuration of the interface, as well as in
case of absence of a network during the installation pha-
se, it is necessary to proceed as follows:
1. connect the interface to your PC via a "cross over" (or
"crossover") network cable
2. access your PC's network settings, as illustrated in
your operating system documentation
3. Change the TCP/IP communication protocol settings
(version 4) for the LAN port of your PC, and set the
following parameters manually:
• IP address: 192.16 8.0.100
• Network mask: 255.255.255.0
• Default gateway: 192.168.0.110
• Save and wait for the new settings to take effect. If
prompted, reboot the system.
After these operations, open an Internet browser and
type in the address bar:
http://192.168.0.110
i
Note! For an optimal browsing experience, we recommend using
one of the following browsers:
• Google Chrome
• Apple Safari
First access
When you open the browser at the default address, the
login screen is displayed:
the voice control interface has the following preset user
at the factory:
User
admin
Enter the credentials of the user "admin" and confirm to
access the main screen of the voice interface administra-
tion environment.
Restore factory IP address
If necessary, you can restore the factory IP address of the
voice interface using the RESET button available. Follow
the procedure below:
• open the front panel of the device using a small slotted
screwdriver, and exerting a slight leverage effect in one
of the side slots
• locate the RESET button on the back of the vertical
card
• Press the button for at least 10 seconds until the SER-
VICE LED on the front of the device starts flashing,
then release the button.
• within the next 5 seconds, press and release the button
for 1 second; within a couple of seconds the front LED
will light up solidly for a couple of seconds
• When the LED goes out, the device can be reached at
the factory IP address (192.168.0.110).
If the LED goes out after long press (10 seconds) before
short press, repeat the whole procedure. This procedure
resets the IP address and retains all data relating to the
configuration previously carried out on the automation sy-
stem.
Restore factory configuration
If the configuration made makes it impossible to access
the server delégo or its correct use, it is possible to re-
store the factory conditions, resetting the IP address and
emptying the supervision project using the "RESET" but-
ton available. In this case, compared to what was pre-
viously seen to restore the IP address, the procedure to
follow is the following:
• open the front panel of the device using a small slotted
• locate the RESET button on the back of the vertical
• Press the RESET button for at least 10 seconds un-
• within the next 5 seconds, press and hold the button for
• When the LED is solidly lit, release the button and wait
• when the LED goes off, remove and restore the power
• Wait about one minute and log in to the server with the
Warning! To avoid losing all the configurations made for the au-
tomation project during a factory reset operation, it is recommen-
ded to make periodic backups of the supervision project.
The configuration and commissioning activities of the KNX voice
control interface require specialized skills on the KNX network
and knowledge of the specific automation project carried out with
ETS. To acquire these skills, it is essential to participate in the
courses organized at KNX certified training centers. For further
information: www.knx.it
Password
admin
Dimensions [mm]
Approvals
• CE the products complie with the Low Voltage Directive
Maintenance
The devices are maintenance-free. To clean them, use
a dry cloth. The use of solvents or other aggressive sub-
stances is absolutely to be avoided.
3
screwdriver, and exerting a slight leverage effect in one
of the side slots
card
til the SERVICE LED on the front of the device starts
flashing, then release the button.
at least 10 seconds
for it to go out.
supply
factory IP address (192.168.0.110).
!
i
36
EK-BW1-TP
Voice control
(2014/35 / EU) and the Electromagnetic Compatibility
Directive (2014/30 / EU). Tests carried out in accordan-
ce with EN 50491-5-1: 2010, EN 50491-5-2: 2010.