bolid S2000-IPDL Installation Manual - Page 4
Browse online or download pdf Installation Manual for Smoke Alarm bolid S2000-IPDL. bolid S2000-IPDL 8 pages. Addressable reflective beam smoke detector
S2000-KDL
4 SETTING ADDRESS
4.1 The detector provides storing its polling loop address in its non-volatile memory. The
factory address of the detector is 127. An address can be given by means of the control panel,
PC software utility, or S2000-APA addressable device programmer (the rules to operate which
are described in its user's manual). An address is assigned to the detector by sending one of
the following commands:
– Set Device Address, or
– Change Device Address.
4.2 The command Set Device Address is used when the detector should be assigned with an
address regardless of which address is given to the detector currently. This way is suitable
when, for example, the same address is assigned with two or more devices. If so, issue a
command to set the required address from the PC or the control panel. Then, within 5 minutes
max since sending the command, press and hold pressed the TEST button of the
detector / remote indicator and control unit for at least 5 second until the red indicator
illuminates. The panel / PC shall display the events of loss of communication with the device
assigned with an old address and finding a device with the new address. If several devices were
assigned with equal addresses set then there will be no messages about loss of
communications for old addresses.
4.3 If however it is necessary to change the detector address which is known in advance then
the Change Device Address command shall be used. Send this command specifying the old
address and the new address from the panel / PC. The panel / PC shall display events about
loss of communication with the device with the old address and establishing communications
with the device with the new address.
5 TESTING THE DETECTOR
5.1.1 A full-range verification of the detector's operability before installation should be done only
in case of mandatory requirements of on-receipt inspection for the products (for example, for
use on special objects) or if you have doubts about its performance (for example, before
sending or after receiving the detector after repair).
5.1.2 If it is impossible or too difficult to pose the transceiver unit and the reflector as far from
each other as required then it is recommended to use the surface of a wall or a ceiling as a
4
Addressable
Addressable
device
device
- PL
+PL
Figure 2. Connection Diagram
5.1 Testing Operability
XT2
XT1
1
- PL
1
2
+PL
2
3
- PL
3
4
+PL
4
XT1
1
2
3
4