bolid S2000-IPDL Installation Manual - Page 6

Browse online or download pdf Installation Manual for Smoke Alarm bolid S2000-IPDL. bolid S2000-IPDL 8 pages. Addressable reflective beam smoke detector

Table 1
LED
Performance
Flashes with
red once per
four seconds
Lit steady with
red
Flashes four
times with red
every four
seconds
Blinking with
red with blue
flashes
--//--
with rare
amber flashes
--//--
with green
flashes
--//--
with amber
flashes
--//--
with white
flashes
Flashes with
red twice per
second
6
Condition
The received signal meets norm
Norm
conditions
Waiting for establishing
communications with the PL
controller
The TEST button has been
Test
pressed
The received signal value has
Fire
dropped down to the alarm
threshold
Programming the detector with an
address
Fire in Progress
The received signal value has
dropped down to the alarm
threshold but the Fire status has
not yet been stated
Operation Mode Changed
Positions of the DIP switches were
changed after exiting the alignment
mode
Establishing of the Test status after
pressing the relevant button
Establishing of the Trouble status
after pressing the relevant button
Trouble in Progress
Conditions for some Trouble status
have occurred but this status has
not yet been established
The TROUBLE button has been
pressed
Trouble-Beam
The received signal has dropped
by more than 80%
Trouble-Out-of-Range
The values written into the
EEPROM are out of the
permissible range
Trouble
Trouble-Memory
Main data and backup data stored
in the EEPROM are not the same
Trouble-High
The compensated signal has
reached the upper threshold
Trouble-Low
The compensated signal has
dropped down to lower threshold
Description
Text on the IPDL-
152 Tester
Display
"Норма" / "Norm"
"Пожар" / "Fire"
"Набор Пож." /
"Fire in Progress"
"Норма" / "Norm"
with "Switched"
from time to time
"Набор Неис." /
"Trouble in
Progress"
"Н. луч" / "TR
Beam"
"Н. допуска" /
"TR Out-of-Range"
"Н. память." /
"TR Memory"
"Н. превыш." /
"TR High"
"Н. снижен." /
"TR Low"