DOTECH FX3DH Series User Manual - Page 5

Browse online or download pdf User Manual for Controller DOTECH FX3DH Series. DOTECH FX3DH Series 9 pages. Digital temp. & humidity controller
Also for DOTECH FX3DH Series: Manual (4 pages)

DOTECH FX3DH Series User Manual
Setting 1 Group
(PRG Button Push for 3 Sec.)
No
Menu
4 0016
Select Control Type
4 0017
Control Deviation Value
4 0018
Select Deviation Value
4 0020
ON Delay Time (※1)
E V 1
4 0021
Minimum OFF Time (※2)
Output
#1
4 0022
Minimum ON Time (※3)
4 0023
Output at Sensor Error (※4)
4 0024
Alarm Deviation Value
4 0025
Alarm Option
4 0026
High limit by user setup
4 0027
Low limit by user setup
4 0028
Manual Output Mode Output (※5)
4 0029
Manual Output Value Output (※6)
4 0031
Select Control Type
4 0032
Control Deviation Value
4 0033
Select Deviation Value
4 0035
ON Delay Time (※1)
E V 2
4 0036
Minimum OFF Time (※2)
Output
#2
4 0037
Minimum ON Time (※3)
4 0038
Output at Sensor Error (※4)
4 0039
Alarm Deviation Value
4 0040
Alarm Option
4 0041
High limit by user setup
4 0042
Low limit by user setup
4 0043
Manual Output Mode Output (※5)
4 0044
Manual Output Value Output (※6)
1) ON delay time : It outputs after setting delay time in spite of output condition. During ON delay time, output lamp is turned on with output after flickering in fast cycle
2) Min OFF Time : It lets output not occur within min. OFF time after it is turned off. During min. OFF time, output lamp is turned on with output after it flickers every 1 second intervals
3) Min ON Time : It is for avoiding frequent ON/OFF of control output and maintains ON condition in spite of OFF condition during Min ON Time after being turned on.
(In case of sensor error, OFF at once)
4) Output at Sensor Error : In case of sensor error such as open wire/short, it sets ON/OFF status of the related output.
5) Manual Output Mode : OFF : Output by PV / ON : Output by
6) Manual Output Value Setup : It outputs continuously regardless of PV. if manual output value is ON when manual output mode is ON. (-R4 model)
Code
Unit
OFF (0) : Display
C (1) : Cooling mode
H (2) : Heating mode
AL I (3) : Deviation high limit alarm
AL2 (4) : Deviation low limit alarm
TY1
AL3 (5) : Deviation high, low limit alarm
AL4 (6) : Deviation high, low limit reverse alarm
AL5 (7) : Absolute value high limit alarm
AL6 (8) : Absolute value low limit alarm
SBA (9) : Sensor open wire alarm
K
DF 1
P (0) : Deviation
TP 1
DT 1
Sec
Sec
FT 1
Sec
NT 1
SF 1
K
H Y 1
ALA (0): General alarm,
A P 1
ALC (2): Standby alarm,
%, °C
U H 1
%, °C
U L 1
OFF (0) : Output by PV
M D 1
(Present Value)
OFF (0) : Always output OFF
M V 1
OFF (0) : Display
C (1) : Cooling mode
H (2) : Heating mode
AL I (3) : Deviation high limit alarm
AL2 (4) : Deviation low limit alarm
TY2
AL3 (5) : Deviation high, low limit alarm
AL4 (6) : Deviation high, low limit reverse alarm
AL5 (7) : Absolute value high limit alarm
AL6 (8) : Absolute value low limit alarm
SBA (9) : Sensor open wire alarm
K
DF 2
P (0) : Deviation
TP 2
Sec
DT 2
Sec
FT 2
Sec
NT 2
SF 2
K
H Y 2
ALA (0): General alarm,
A P 2
ALC (2): Standby alarm,
%, °C
U H 2
%, °C
U L 2
OFF (0) : Output by PV
M D 2
(Present Value)
OFF (0) : Always output OFF
M V 2
MVI,MV2
(-R4 model)
- 5 -
Step
Min
0.1
0.1
PN (1): ± Deviation
1
0
1
0
1
0
OFF (0)
0N (1)
0.1
0.0
ALB (1): Maintain alarm,
ALD (3): Maintain & standby alarm
1
U L 1
1
-50
U H 1
ON (1) : Output by MV2
(-R4 model)
ON (1) : Always output ON
0.1
0.1
PN (1): ± Deviation
1
0
1
0
1
0
OFF (0)
0N (1)
0.1
0.0
ALB (1): Maintain alarm,
ALD (3): Maintain & standby alarm
1
U L2
1
-50
U H 2
ON (1) : Output by MV2
(-R4 model)
ON (1) : Always output ON
Max
Default
Custom Setup
C (1)
99.9
2.0
P (0)
999
1
999
5
999
5
OFF (0)
99.9
1 .0
ALA (0)
1 05
1 00
0
OFF (0)
OFF (0)
H (2)
99.9
2.0
P (0)
999
1
999
5
999
5
OFF (0)
99.9
1 .0
ALA (0)
1 05
1 00
0
OFF (0)
OFF (0)
R20160613