Baumer IO-Link RR30 Instruction Manual - Page 9

Browse online or download pdf Instruction Manual for Accessories Baumer IO-Link RR30. Baumer IO-Link RR30 40 pages. Radar sensor

Baumer IO-Link RR30 Instruction Manual
Value of MDC
-
Unit
-
Scale
-
Measured value
-
Bit 16 to 47: MDC
MDC stands for measurement data channel. It contains the already filtered date arising from SSC1 to SSC4
as an 32 bit integer value. See section 4.2 to learn how to configure the MDC.
Bit 48 to 207 : Peak Data
Peak data is the main measurement data. The values are the first 5 peaks from the defined Region of
Interest (all further peaks are ignored) transmitted as two 16 bit values: 16 bit for the amplitude and 16 bit for
the distance. The Amplitude in dB shows the relative strength of the signal and the distance is displayed in
mm.

Process Data-Out

3.2.2
This data is cyclically sent from the master to the sensor (MasterSensor).
7
6
5
Bit 0: Disable Radar antenna (Transducer)
By changing this bit the antenna is disabled. This switches off the sensing (receiving) element without switching
off the whole electronic of the sensor. The sensor output will be frozen for all distance and amplitude values.
This can be used to reduce the heating of the sensor itself.
Bit 0 = 0 → Radar antenna is enabled
Bit 0 = 1 → Radar antenna is disabled
Bit 1: Find Me Function
Signaling e.g. by flashing LEDs (green and yellow) on the sensor to locate or physically identify a sensor in a
machine or system.
Bit 1 = 0 → Find Me Function is deactivated
Bit 1 = 1 → Find Me Function is activated, LEDs are flashing.
en_BA_RR30_IO-Link_V0.23.docx
13.01.2021/
1000
m
-6
m or 1000 m
1000*10
-6
IO-Link Process Data Output
4
3
2
Bit:
1
Find Me (Localization: green
and yellow LED flashing)
9/40
0
Disable Radar
antenna
Baumer Electric AG
Frauenfeld, Switzerland